My consumption is displayed incorrectly in FusionSolar or gives incorrect values.

Please check the wiring of the Smart Power Sensors again.

Here it is important that the following points are observed:

  • The Smart Power Sensor always sits behind all loads.
  • The arrow direction of the current clamps must always point to the loads or into the house.
  • The phase assignment of the voltage tap, which is terminated at the top of the sensor, must match the current tap on the underside of the sensor.

If there is another energy generator in the grid, it cannot communicate with the Smart Power Sensor. This means that incorrect values are transmitted to the FusionSolar.