Buy LevelX Energy Blackout-Box Compact from SKE
Why should you choose a LevelX Energy Blackout-Box Compact now?
The new LevelX Blackout-Box Compact ensures a 24/7 backup supply for critical loads in the building. Switchover in the event of a blackout is fully automatic within 5 seconds and ensures the operation of single-phase emergency power consumers up to 3,300 VA.
The LevelX blackout box is compatible with Huawei SUN2000-3/4/5/6/8/10KTL-M1 inverters and HUAWEI LUNA2000 storage batteries, fulfills the FRT capability according to the Austrian TOR generator type A and can be retrofitted in the PV system at any time.
The dimensions of the new Black-out Box Compact make it easy to install in the distribution box.
- For 220/230V networks
- Single-phase emergency power output
- 3300 VA output
- Compact device
Secure
Easy to install on site
Smart
Automatic switching
Reliable
Power supply for critical consumers even in the event of a power failure
LevelX Energy Blackout-Box Compact- Technical specifications
All facts and figures are summarised for you in a compact and up-to-date form at.
LevelX Energy Blackout-Box Compact - General data
Betriebstemperaturbereich: -5 bis +40 °C Relative Luftfeuchtigkeit im Betrieb: <95 %
Normen: EN 61439-1, EN61439-3, RoHS, REACH
Konformität: TOR Erzeuger Typ A (FRT-Fähigkeit für Österreich)
Abmessungen (HxBxT) : 382 x 210 x 170 mm
Gewicht: 6 kg
Schutzart: IP 2XC
Zählerverteiler auf einer freien Zählertafel
LevelX Energy Blackout-Box Compact - AC connection - Backup consumer
Mains connection: Single-phase (L/N/PE)
Operating voltage: 230 V AC
Mains frequency: 50 Hz
Max. Apparent power: 3300 VA (SUN2000-3KTL-M1 > 3000 VA)
Max. output current: 15.2 A
Switchover time: 5 seconds
Integrated RCD: Type A, selective, 100 mA
LevelX Energy Blackout-Box Compact - AC connection (inverter)
Connection: Three-phase (3P/N/PE)
Nominal voltage: 230 / 400 V AC / 50 Hz
Compatible inverters: SUN2000-3~10KTL-M1
LevelX Energy Blackout-Box Compact AC connection (mains cable)
Mains type: Three-phase (3P/N/PE)
Nominal voltage: 230V / 400V AC / 50 Hz
Valid mains forms: TT, TN-S
Mains disconnection: 3- or 4-pole (configurable via jumper)
Max. permissible back-up fuse: 25 A